Sign In | Join Free | My benadorassociates.com |
|
Brand Name : LESER
Model Number : Type 811
Place of Origin : Germany
MOQ : 1 set
Payment Terms : T/T, D/A, L/C, D/P, Western Union
Supply Ability : 50 SETS/MONTH
Delivery Time : 6~8 WEEKS
Packaging Details : Carton
Nominal Diameter at Inlet : DN 25 - DN 200 | 1" - 8"
Orifice : API Standard as well as Extra Orifice: 1 D 2 - 8 T 10 / 1 G 2 - 8 T+ 10
Actual Orifice Diameter d₀ : 11 - 190 mm | 0.433 - 7.087 in
Actual Orifice Area A₀ : 95 - 25446.9 mm² | 0.147 - 39.443 in²
Pressure : 2.5 - 256 bar | 36 - 3705 psig
Flange Rating Inlet : PN 10 - PN 250 | CL150 - CL1500
Temperature (in accordance with DIN EN) : -45 to 200 °C (Special: -162 to 300 °C) | -49 to 392 °F (Special: -259.6 to 572 °F)
Temperatur (nach ASME) : -45 to 200 °C (Special: -162 to 300 °C) | -49 to 392 °F (Special: -259.6 to 572 °F)
Body Material : 1.0619, 1.4408 (Special: Hi Alloy) | SA 216 WCB, SA 351 CF8M, SA 352 LCB (Special: Hi Alloy)
Valve Connection : Flange acc. to DIN EN 1092 or acc. to ASME B 16.5 or acc. to JIS 2220
Load Type : Controlled by process medium
Specials : Pilot action type: Pop Action | Open: 1% opening pressure tolerance | Closed: 3 - 7% (adjustable also beyond API standard from 3 up to 15%) closing pressure tolerance | Application: Gas
Approvals : ASME Sec. VIII Div. 1, PED/ DIN EN ISO 4126-4, PED/ AD 2000-Merkblatt A2, AQSIQ, EAC, TSSA
Classification societies : LR, RINA, DNV GL, BV
Pop Action Type 811 High Efficiency Pilot operated Safety Valve
Solutions for high plant efficiency
Pilot operated safety valves
Highest blow-off capacity of all series
Tightness right up to set pressure
Operating pressures up to 96% of the set pressure
Back pressures up to 70% of the set pressure
Backflow preventer integrated as a standard component
Integrated Piping prevents damage and freezing
Supplementary Loading System
Equipment that enables the following safety valve characteristics:
Tightness right up to set pressure
Operating pressures up to 97% of the set pressure
Low loss of medium due to short opening times
Function test and valve adjustment possible during operation
Suitable for all media temperatures
Pop Action Type 811 High Efficiency Pilot Operated Safety Valve Images |